- Color & Paint Coating Measurement
- Dimensional Measurement
- Electrical & Electronic Meter
- Electrostatics (ESD) , Ionizer & Resistivity Meter
- Environmental & Weather Aging Testing
- Gas Measurement
- Handling & Cutting Tools
- Hardness Testing
- Laboratory Equipments
- Levelling Angle Gauges
- Magnetic Testing
- Medical Equipment
- Metallography
- Microscope, Magnifier & Visual Inspection
- Paper & Film Packaging Testing
- Pressure & Flow
- Rubber & Glove Testing
- Storage Dry Cabinet
- Temperature, Humidity & Moisture
- Tensile & Tension Torque/Force
- Ultrasonic NDT Testing
- Vise & Holder
- Water Analysis Meter
- Weighing
- Others
Fluke - 116 Digital HVAC Multimeter
Previous | 452 / 498 | Next |
Fluke - 116 Digital HVAC Multimeter
Brand : Fluke
Model : 116
The Fluke 116 was specifically designed for HVAC professionals. It has everything you need to quickly troubleshoot problems with HVAC equipment and flame sensors, including a built-in thermometer to measure temperatures up to 400°C (752°F) and microamps to test flame sensors. The Fluke 116 also measures resistance, continuity, frequency, and capacitance. And the large white LED backlight makes it easy to see results even in poorly lit areas.
Fluke 116 multimeters are independently tested for safe use in CAT III 600 V environments.
Features
Specifications
Brand : Fluke
Model : 116
The Fluke 116 was specifically designed for HVAC professionals. It has everything you need to quickly troubleshoot problems with HVAC equipment and flame sensors, including a built-in thermometer to measure temperatures up to 400°C (752°F) and microamps to test flame sensors. The Fluke 116 also measures resistance, continuity, frequency, and capacitance. And the large white LED backlight makes it easy to see results even in poorly lit areas.
Fluke 116 multimeters are independently tested for safe use in CAT III 600 V environments.
Features
- Digital multimeter designed specifically for HVAC professionals
- Includes built-in thermometer to measure temperature from -40°C to 400°C (-40°F to 752°F)
- Provides microamps to test flame sensors
- Features low input impedance to helps prevent false readings due to ghost voltage
- Presents a large white LED backlight for working in poorly lit areas
- Measures resistance, continuity, frequency, and capacitance
- Provides Min/Max/Average to record signal fluctuations
- Comes with a holster with probe holders for easy storage
- Features a compact ergonomic design for one-handed operation
- Fits into optional ToolPak™ magnetic hanger for hands-free operation
- CAT III 600 V safety rated
Specifications
Specifications | ||
Maximum voltage between any terminal and earth ground | 600 V | |
Safety |
IEC 61010-1: Pollution Degree 2 IEC 61010-2-033: CAT III 600V |
|
Display | Digital: 6,000 counts, updates 4 per second | |
Bar graph | 33 segments, updates 32 per second | |
Operating temperature | -10°C to + 50°C | |
Storage temperature | -40°C to + 60°C | |
Battery type | 9 volt Alkaline, IEC 6LR61 | |
Battery life | 400 hours typical, without backlight | |
Accuracy Specifications | ||
DC millivolts | Range/resolution | 600.0 mV / 0.1 mV |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
DC volts | Range/resolution |
6.000 V / 0.001 V 60.00 V / 0.01 V 600.00 V / 0.1 V |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
Auto volts | Range/resolution | 600.0 V / 0.1 V |
Accuracy |
2.0% + 3 (DC, 45 Hz to 500 Hz) 4.0% + 3 (500 Hz to 1 kHz) |
|
AC millivolts1 True RMS | Range/resolution | 600.0 mV / 0.1 mV |
Accuracy |
1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) |
|
AC volts1 True RMS | Range/resolution |
6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V |
Accuracy |
1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) |
|
Continuity | Range/resolution | 600 Ω / 1 Ω |
Accuracy |
Beeper on < 20 Ω, off > 250 Ω detects opens or shorts of 500 μs or longer. |
|
Ohms | Range/resolution |
600.0 Ω / 0.1 Ω 6.000 kΩ / 0.001 kΩ 60.00 kΩ / 0.01 kΩ 600.0 kΩ / 0.1 kΩ 6.000 MΩ / 0.001 MΩ |
Accuracy | 0.9% + 1 | |
Range/Resolution | 40.00 MΩ / 0.01 MΩ | |
Accuracy | 5% + 2 | |
Diode Test | Range/resolution | 2.00 V / 0.001 V |
Accuracy | 0.9% + 2 | |
Capacitance | Range/resolution |
1000 nF / 1 nF 10.00 μF / 0.01 μF 100.0 μF / 0.1 μF 9999 μF / 1 μF 100 μF to 1000 μF |
Accuracy | 1.9% + 2 | |
Range/resolution | > 1000 μF | |
Accuracy | 5% + 20% | |
Lo-Z Capacitance | Range | 1 nF to 500 μF |
Accuracy | 10% + 2 typical | |
Temperature² (Type-K thermocouple) |
Range/resolution | -40°C to 400°C / 0.1°C |
Accuracy | 1% + 10² | |
Range/resolution | -40°F to 752°F / 0.2°F | |
Accuracy | 1% + 18² | |
AC μA true-rms (45 Hz to 500 Hz) | Range/resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.5% + 3 | |
DC μamps | Range/resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.0% + 2 | |
Hz (V or A input)² | Range/resolution |
99.99 Hz / 0.01 Hz 999.9 Hz / 0.1 Hz 9.999 kHz / 0.001 Hz 50.00 kHz / 0.01 Hz |
Accuracy | 0.1% + 2 | |
1. All AC voltage ranges except Auto-V/LoZ are specified from 1% to 100% of range. Auto-V/LoZ is specified from 0.0 V. 2. Temperature uncertainty (accuracy) does not include the error of the thermocouple probe. 3. Frequency is AC coupled, 5 Hz to 50 kHz for AC voltage. Frequency is DC coupled, 45 Hz to 5 kHz for AC current. 4. Temperature Range/Resolution: -40°F to 752°F / 0.2°F. |
||
Mechanical and General Specifications | ||
Size | 167 x 84 x 46 mm (6.57 x 3.31 x 1.82 in) | |
Weight | 550 g | |
Warranty | 3 years |