Visit
Official Website

Fluke - 438-II Power Quality and Motor Analyzer

Previous 33 / 86 Next


Fluke - 438-II Power Quality and Motor Analyzer
Brand : Fluke
Model : 438-II

 
The Fluke 438-II Power Quality and Motor Analyzer adds key mechanical measurement capabilities for electric motors to the advanced power quality analysis functions of the Fluke 435 Series II Powe Quality Analyzers. Quickly and easily measure and analyze key electrical and mechanical performance parameters such as power, harmonics, unbalance, motor speed, torque and mechanical power without the need of mechanical sensors. Fluke 434-II, 435-II and 437-II Power Quality Analyzer users can add motor analysis capabilities to their existing units with the Fluke-438-II/MA Motor Analyzer upgrade kit. The 438-II uses data from the motor rating plate for either NEMA or IEC rated motors to aid the calculation of the mechanical parameters.
 
Features:
  • Calculates mechanical power and efficiency without mechanical sensors. Just connect to the input conductors
  • Measures electrical power parameters such as voltage, current, power, apparent power, power factor, harmonic distortion and unbalance to identify characteristics that impact motor efficiency
  • Identify power quality issues such as dips, swells, transients, harmonics and unbalance
  • Uses PowerWave data capture to capture fast RMS data, and show half-cycle averages and waveforms to characterize electrical system dynamics (generator start-ups, UPS switching etc.)
  • Offers waveform capture function to capture 100/120 cycles (50/60 Hz) of each detected event, in all modes, without set-up
  • Uses automatic transient mode to capture waveform data at 200 kS/s on all phases simultaneously up to 6 kV
  • Automatically calculate motor derating according to NEMA/IEC guidelines
 
Specifications:
 
Specifications
Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory 8GB SD card (SDHC compliant, FAT32 formatted), up to 32GB optionally. Screen save and multiple data memories for storing data including recordings (dependent on memory size).
Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture
Environmental
Operating Temperature 0°C ~ +40°C; +40°C ~ +50°C excl. battery
Storage Temperature -20°C ~ +60°C
Humidity +10°C ~ +30°C: 95% RH non-condensing
+30°C ~ +40°C: 75% RH non-condensing
+40°C ~ +50°C: 45% RH non-condensing
Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on accessories
1. ±5% if ≥ 1% of nominal voltage ±0.05% of nominal voltage if < 1% of nominal voltage
2. 50Hz/60Hz nominal frequency according to IEC 61000-4-30
3. 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode
4. For nominal voltage 50 V to 500 V